Selec EM4M-3P-C-100A Three-Phase Multifunction Meter
Selec EM4M-3P-C-100A | 3-Phase Multifunction Energy Meter (100A Direct)
Compact Class-1 3-phase multifunction energy meter with 100A direct measurement, RS-485 Modbus RTU, pulse output, load monitoring, MD measurement, and LCD display for industrial and commercial applications.
The Selec EM4M-3P-C-100Ais a compact 3-phase multifunction energy meter designed for direct 100A applications without CTs. Equipped with RS-485 Modbus RTU, pulse output, LCD display, Class-1 accuracy, and maximum demand monitoring, it is ideal for industrial panels, commercial systems, load management, and energy auditing.
(All features verified from pages 1–4 of the EM4M manual.)
Key Features
3-phase, 3-wire / 4-wire True RMS measurement
Direct 100A measurement (no CT required)
Measures V, A, PF, Frequency, kW/kVAr/kVA, kWh/kVArh/kVAh
LCD display with backlight
RS-485 Modbus RTU communication
Pulse output for PLC/BMS integration
Maximum demand (MD) measurement
Programmable display parameters
Password protection for settings
1-second update rate
DIN-rail mountable compact design
(From manual page 1 & 2)
3-phase, 3-wire / 4-wire True RMS measurement
Direct 100A measurement (no CT required)
Measures V, A, PF, Frequency, kW/kVAr/kVA, kWh/kVArh/kVAh
LCD display with backlight
RS-485 Modbus RTU communication
Pulse output for PLC/BMS integration
Maximum demand (MD) measurement
Programmable display parameters
Password protection for settings
1-second update rate
DIN-rail mountable compact design
(From manual page 1 & 2)
Technical Specifications (Table)
Parameter Specification Model EM4M-3P-C-100A Wiring System 3Ø-4W / 3Ø-3W Voltage Range 176–276V L-N, 304–480V L-L Current Range Direct 100A (Imax), Ib = 10A, Imin = 0.5A Frequency 45–65 Hz Display LCD with backlight, 4 digits Display Update Time 1 second Active Energy Accuracy Class-1 Reactive Energy Accuracy Class-2 Voltage Accuracy ±0.5% FS Current Accuracy ±0.5% FS Power Accuracy ±1% FS PF Accuracy ±0.01 Pulse Output 24 VDC max, 100 mA Pulse Weight 1 / 10 / 100 / 1000 pulses Communication RS-485 Modbus RTU Baud Rate 9600 / 19200 Parity None / Odd / Even Stop Bits 1 or 2 Transmission Distance Up to 500 m Power Consumption < 8 VA Operating Temperature –10°C to 55°C Humidity Up to 85% RH non-condensing Mounting DIN Rail Dimensions 114 × 106 × 74 mm Weight 320 g (All verifier values: EM4M manual pages 1–3)
| Parameter | Specification |
|---|---|
| Model | EM4M-3P-C-100A |
| Wiring System | 3Ø-4W / 3Ø-3W |
| Voltage Range | 176–276V L-N, 304–480V L-L |
| Current Range | Direct 100A (Imax), Ib = 10A, Imin = 0.5A |
| Frequency | 45–65 Hz |
| Display | LCD with backlight, 4 digits |
| Display Update Time | 1 second |
| Active Energy Accuracy | Class-1 |
| Reactive Energy Accuracy | Class-2 |
| Voltage Accuracy | ±0.5% FS |
| Current Accuracy | ±0.5% FS |
| Power Accuracy | ±1% FS |
| PF Accuracy | ±0.01 |
| Pulse Output | 24 VDC max, 100 mA |
| Pulse Weight | 1 / 10 / 100 / 1000 pulses |
| Communication | RS-485 Modbus RTU |
| Baud Rate | 9600 / 19200 |
| Parity | None / Odd / Even |
| Stop Bits | 1 or 2 |
| Transmission Distance | Up to 500 m |
| Power Consumption | < 8 VA |
| Operating Temperature | –10°C to 55°C |
| Humidity | Up to 85% RH non-condensing |
| Mounting | DIN Rail |
| Dimensions | 114 × 106 × 74 mm |
| Weight | 320 g |
| (All verifier values: EM4M manual pages 1–3) |
Applications
Industrial 3-phase energy monitoring
Commercial building metering
HVAC load measurement
DG panel monitoring
Solar and renewable load monitoring
Smart building, BMS, EMS
Sub-metering for industrial loads
Industrial 3-phase energy monitoring
Commercial building metering
HVAC load measurement
DG panel monitoring
Solar and renewable load monitoring
Smart building, BMS, EMS
Sub-metering for industrial loads
What’s in the Box
Selec EM4M-3P-C-100A Meter
User Instruction Manual
DIN-rail mounting clip
Warranty card
Selec EM4M-3P-C-100A Meter
User Instruction Manual
DIN-rail mounting clip
Warranty card
FAQ
Q1: Does EM4M require external CTs?
No—it supports 100A direct measurement.
✔ Verified from manual.
Q2: Does this meter support Modbus?
Yes, it supports RS-485 Modbus RTU (9600/19200 bps).
✔ Listed under the communication section.
Q3: Is it Class-1 accuracy?
Yes—Active Energy Accuracy is Class-1 (IEC).
✔ Verified from technical table.
Q4: What pulse output does it provide?
Pulse output supports 24V DC, 100 mA, and a pulse weight of 1–1000 pulses.
✔ From pulse output specification.
Q5: Can it measure maximum demand?
Yes—EM4M displays MD (kW / kVAr / kVA).
✔ Verified from display menu.
Q6: How is the meter mounted?
It is DIN-rail mountable with a compact enclosure.
✔ From mechanical drawing.