Wall Mount Single Gas Monitor with LCD Display and Alarm | RDCL-SGM
The RDCL-SGM Wall Mount Single Gas Monitor with LCD Display and Alarm is an industrial fixed gas detection instrument designed for continuous monitoring of toxic and hazardous gas concentrations. Equipped with a high sensitivity electrochemical sensor, real time LCD display, audible and visual alarms, and RS485 Modbus RTU communication, it provides reliable gas monitoring for industrial safety applications. Supporting multiple gas detection options including O2, CO, H2S, NH3, NO2, SO2, O3, H2 and PH3, the monitor features customizable measurement ranges, remote parameter configuration and a 10 to 30V DC power supply. It is suitable for chemical plants, refineries, petrochemical industries, metallurgy, power plants and industrial gas monitoring systems.
Customize
Share :
A. Product Overview
The RDCL-SGM Wall Mount Single Gas Monitor with LCD Display and Alarm is an industrial device designed for continuous monitoring of one selected gas in ambient air. It uses electrochemical sensing technology for supported gases and provides audible and visual alarms when configured concentration limits are reached.
The monitor supports oxygen, carbon monoxide, hydrogen sulfide, ammonia, nitrogen dioxide, sulfur dioxide, ozone, hydrogen and phosphine. Its LCD display shows real time gas readings, while RS485 Modbus RTU communication enables integration with PLC, SCADA and industrial monitoring systems.
Key Features
Continuous monitoring of one selected gas
Electrochemical sensing for supported gas configurations
LCD display with audible and visual alarms
Configurable alarm thresholds
RS485 Modbus RTU communication
Adjustable device address and baud rate
Communication distance up to 2000 meters
Infrared remote parameter configuration
Power supply: 10 to 30V DC
Wall mounted industrial enclosure
Technical Specifications
Parameter | Specification |
|---|---|
Model | RDCL-SGM |
Product Type | Wall Mount Single Gas Monitor |
Detection | One Selected Gas |
Sensing | Electrochemical for supported gases |
Display | LCD |
Alarm | Audible and Visual |
Output | RS485 Modbus RTU |
Communication Distance | Up to 2000 meters |
Configuration | Infrared Remote Control |
Power Supply | 10 to 30V DC |
Power Consumption | 0.6W at 24V DC |
Operating Temperature | −10°C to 50°C |
Operating Humidity | 15% to 90% RH, non-condensing |
Warm Up Time | At least 5 minutes |
Installation | Wall Mount |
Available Gas Detection Options
Gas | Formula | Measurement Range |
|---|---|---|
Oxygen | O2 | 0 to 30% VOL |
Carbon Monoxide | CO | 0 to 1000 or 2000 ppm |
Hydrogen Sulfide | H2S | 0 to 100 ppm |
Ammonia | NH3 | 0 to 50 or 100 ppm |
Nitrogen Dioxide | NO2 | 0 to 20 or 2000 ppm |
Sulfur Dioxide | SO2 | 0 to 20 or 2000 ppm |
Ozone | O3 | 0 to 100 ppm |
Hydrogen | H2 | 0 to 1000 ppm |
Phosphine (PH3) is also supported. Confirm its measurement range before ordering.
Note: Each RDCL-SGM monitors only one selected gas. Multiple gas monitoring requires separate units or a dedicated multi gas system.
B. Working Principle
The RDCL-SGM uses electrochemical sensing technology for supported gases to convert gas concentration into an electrical signal.
1. Gas Detection: The selected gas enters the sensing element through a gas permeable interface.
2. Electrochemical Reaction: The target gas reacts at the sensing electrode, generating a signal related to its concentration.
3. Signal Processing: Internal electronics convert the signal into gas concentration, generally expressed in ppm or percentage by volume.
4. LCD Display: The measured gas concentration appears on the built in LCD screen.
5. Alarm Activation: Audible and visual alarms activate when the configured alarm condition is detected.
6. RS485 Communication: Measurements are transmitted through Modbus RTU to compatible PLC, SCADA and monitoring systems.
7. Remote Configuration: Infrared remote control allows supported parameters to be adjusted without opening the enclosure.
C. Why Is the RDCL-SGM Used?
The RDCL-SGM provides continuous gas monitoring and local warning indications in industrial environments where hazardous gases may be present.
1. Industrial Gas Leakage Detection: Helps identify abnormal gas concentrations in processing, storage and handling facilities.
2. Workplace Safety Monitoring: Supports monitoring of toxic gases and oxygen concentrations in industrial workplaces.
3. Audible and Visual Alarms: Provides local warning when configured gas concentration thresholds are reached.
4. Continuous Monitoring: Enables fixed gas measurement without repeated handheld testing.
5. Oxygen Monitoring: Supports monitoring of oxygen deficient or enriched conditions with an oxygen configured unit.
6. Chemical Plant Monitoring: Measures selected gases such as ammonia, hydrogen sulfide, carbon monoxide and sulfur dioxide.
7. Industrial Automation: Integrates gas readings into PLC, SCADA and centralized monitoring systems.
Industrial Applications
Chemical and petrochemical industries
Petroleum refineries
Metallurgical processing plants
Power generation facilities
Industrial gas storage and handling
Manufacturing and processing plants
Industrial equipment rooms
Gas detection and ventilation systems
PLC and SCADA monitoring installations
Safety Note: Hazardous area installations and personnel protection applications require verification of the instrument's certifications, suitability and applicable safety requirements.
D. Suitable Buyers
Suitable Buyers | Applications |
|---|---|
Chemical Plant Operators | Hazardous gas monitoring |
Petroleum Refineries | Process gas monitoring |
Petrochemical Industries | Fixed gas detection |
Industrial Safety and EHS Teams | Workplace gas monitoring |
Automation Integrators | PLC and SCADA integration |
Power Plant Maintenance Teams | Industrial gas monitoring |
OEM Manufacturers | Gas monitoring equipment |
EPC Contractors | Industrial monitoring projects |
Instrumentation Engineers | Fixed gas monitoring installations |
Gas Handling Industries | Storage and processing monitoring |
Industrial Procurement Teams | Gas detection equipment sourcing |
E. Frequently Asked Questions
1. What is the RDCL-SGM Single Gas Monitor?
The RDCL-SGM is a wall mounted industrial gas monitor that measures one selected gas and provides audible and visual alarms.
2. Which gases can it detect?
Oxygen, carbon monoxide, hydrogen sulfide, ammonia, nitrogen dioxide, sulfur dioxide, ozone, hydrogen and phosphine.
3. Can it detect multiple gases simultaneously?
No. Each unit monitors one selected gas. Multiple gases require separate monitors or a multi gas detection system.
4. Does it have an LCD display?
Yes. The LCD displays measured gas concentration in real time.
5. Does it provide audible and visual alarms?
Yes. Both alarm indications activate when configured alarm conditions are met.
6. What communication output is available?
RS485 digital communication using Modbus RTU protocol.
7. Can it connect to PLC and SCADA systems?
Yes. Compatible PLC and SCADA systems can receive readings through RS485 Modbus RTU.
8. What power supply is required?
10 to 30V DC, with approximately 0.6W consumption at 24V DC.
9. Can settings be changed remotely?
Yes. Infrared remote control supports adjustment of selected parameters.
10. What is the maximum communication distance?
Up to 2000 meters under suitable wiring and installation conditions.
11. What is the operating temperature range?
−10°C to 50°C.
12. Is it suitable for continuous industrial monitoring?
Yes. It is designed for continuous monitoring of one selected gas in suitable industrial environments.